Putting a Stop to Energy Waste
®
00335r1 5/99
TECH SUPPORT
The Watt Stopper, Inc.
2800 De La Cruz Blvd.
Santa Clara, CA 95050, USA
Tel: 1(800)879-8585 1(972)578-1699
Fax: 1(972)422-1311
www.wattstopper.com
Santa Clara, CA 95050
(800) 879-8585
Installation Instructions
U.S.Patents:
4,787,722
5,640,113
Model#s:
EW-100-120
EW-105-120
EW-200-120
EW-205-120
EW-100-277
EW-105-277
EW-200-277
EW-205-277
Outdoor 180° & 270° PIR
Motion Sensors
SPECIFICATIONS
Voltage:
EW-100-120, EW-105-120, EW-200-120, EW-205-120 . . . . . . . . 120VAC, 60Hz
EW-100-277, EW-105-277, EW-200-277, EW-205-277 . . . . . . . . 277VAC, 60Hz
Mountable Locations . . . . . . . . . . . . . . . . . . . . . . . . . Wall, ceiling or under eaves
Operating Temperature . . . . . . . . . . . . . . . . . . . . . . -40° to 130°F (-40° to 55°C)
Lens Coverage:
EW-100 & EW-105 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180°
EW-200 & EW-205. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270°
Load Ratings . . . . . . . . . . . . . . . . . . . . . . 0–1000W ballast or tungsten @120VAC
0–1000W ballast @277VAC
Motor Load: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/6 HP @120VAC
1/3 HP @277VAC
Current Consumption
Without Isolated Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 mA max.
With Isolated Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 mA max.
Time Delay Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12sec.–16min.
Light Level Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5FC–200FC
Isolated Relay on EW-100 & EW-200 (both -120 & -277 models)
Normally Open & Normally Closed contacts.
Isolated Relay Rating: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1A @ 30VAC/DC
UL 773A Raintight Rated
IEC-IP-55 Rated
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Installation Instructions

Putting a Stop to Energy Waste®00335r1 5/99TECH SUPPORTThe Watt Stopper, Inc.2800 De La Cruz Blvd.Santa Clara, CA 95050, USATel: 1(800)879-8585 1(9

Page 2 - ≠CAUTION ≠

1BOX CONTENTS• One (1) EW-100-120, EW-105-120, EW-200-120, EW-205-120,EW-100-277, EW-105-277, EW-200-277 or EW-205-277• Accessory bag:- Cover plate fo

Page 3 - Horizontally mounted:

MOTION SENSOR PLACEMENTCareful consideration must be given to sensor placement. PIR sensors detect the differencebetween infrared energy in motion and

Page 4 - ≠CAUTION≠

WIRING AND INSTALLATION≠CAUTION≠TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING SENSOR.SENSOR MUST BE INSTALLED BY QUALIFIED PERSONNEL ONLY.4&

Page 5 - TESTING AFTER INSTALLATION

1. Adjust Time Delay:The time delay is the amount of time that elapses before lights turn off since the sensor last detected motion. This can be set f

Page 6

Check Our Web Site For FAQs: www.wattstopper.com9SECURITY OVERRIDEThe EW sensors have an override-on feature which allows lights to be turned on for t

Comments to this Manuals

No comments